Average daylight factor (BRE / CIBSE method) for a rectangular room, with window ratios, the room depth rule and a no-sky line estimate.
Below 2 %: the room is likely to look gloomy and need electric light for most of the day.
| Check | Target | This room | Result |
|---|---|---|---|
| BS 8206-2:2008 minimum ADF, living room (withdrawn, still widely cited) | 1.5 % | 1.72 % | ✓ meets |
| NCC 2022 Vol. Two H4P4, habitable room (Australia) | 2 % | 1.72 % | ✗ below |
| EN 17037 minimum level, DT = 300 lx / 14900 lx (Prague, CZ). Indicative: EN 17037 uses the value exceeded over half of the plane, not the mean | 2.01 % | 1.72 % | ✗ below |
| UK National Annex to BS EN 17037, living room: 150 lx over half of the plane (BR 209:2022), divided by the median illuminance chosen below (14900 lx). No UK value is built in: choose Custom and enter your UK site value. Indicative, same caveat | 1.01 % | 1.72 % | ✓ possible |
| Working plane with direct sky (no-sky line, d = x h / y), CSH 2010 Hea 1, continuous obstruction parallel to the window | 80 % | 100 % | ✓ meets |
| Room depth rule L/W + L/H ≤ 2/(1 − Rb), windows in one wall (BS 8206-2, BR 209). Rb = 0.55, max depth 6.60 m | ≤ 4.40 | 3.33 | ✓ meets |
| NCC 2022 Housing Provisions 10.5.1: glass area ≥ 10 % of floor (windows) or 3 % (roof lights), combined in proportion | ≥ 100 % | 153.6 % | ✓ meets |
| Wall | Windows | Opening | Wall | WWR |
|---|---|---|---|---|
| Front (S) | 1 | 3.84 m² | 10.80 m² | 35.6 % |
| Back (N) | 0 | 0.00 m² | 10.80 m² | 0.0 % |
| Left (W) | 0 | 0.00 m² | 13.50 m² | 0.0 % |
| Right (E) | 0 | 0.00 m² | 13.50 m² | 0.0 % |
| # | Position | Aw (net) | T | θ | M | DF |
|---|---|---|---|---|---|---|
| 1 | Front wall | 3.07 m² | 0.60 | 59.4° | 1.00 | 1.72 % |
Simplified hand calculation. The average daylight factor formula assumes a CIE overcast sky, a simple rectangular room and continuous obstructions. It does not replace a daylight simulation. For climate based metrics (the EN 17037 illuminance method, sDA, UDI) use validated Radiance based tools, compared in our guide to daylight analysis software. Targets are shown for information only; check the edition in force and the local authority.
The daylight factor tells you how bright a room will be under an overcast sky, as a percentage of the light outside. This daylight factor calculator uses the average daylight factor formula from the BRE and CIBSE guidance to test a room with several windows and roof lights in seconds. It also gives the window to floor ratio, the window to wall ratio of each facade, the room depth rule and a no-sky line estimate, with a section and plan you can export.
The calculator runs in your browser and nothing is uploaded. It remembers your last room on this device, and Reset takes you back to the default.
The calculator uses the formula given in the Code for Sustainable Homes technical guidance (after BS 8206-2 and the Littlefair method), the same expression the Australian NCC uses for its daylight verification method:
DF = T × Aw × θ × M / (A × (1 − R²)), in percent.
Each window is calculated on its own and the results are added, so windows with different glass or obstructions are handled correctly. A table shows each window’s net area, T, θ, M and contribution.
A quick hand check: a 3 × 4 × 2.4 m room has 57.6 m² of surfaces. A 1.2 × 1.2 m window with no frame gives 1.44 m² of glass. With T 0.7, θ 65 degrees, M 1 and a mean reflectance of 0.5, the result is 0.7 × 1.44 × 65 / (57.6 × 0.75) = 1.52%.
The default room, a 4 × 5 × 2.7 m living room with one 2.4 × 1.6 m low-E window facing a 20 degree obstruction, comes out at 1.72%: above the 1.5% living room minimum, below the 2% figure used in Australia.
The calculator places every result in one of three bands. Below 2%, a room is likely to look gloomy and need electric light for most of the day. From 2% to 5% it is predominantly daylit, though some supplementary electric light is still needed. At 5% or more it is strongly daylit and electric light is rarely needed, but check glare and heat gain.
For homes, the minimum average daylight factors most often quoted come from BS 8206-2:2008: 2% for a kitchen, 1.5% for a living room, dining room or study, and 1% for a bedroom. An open plan living room and kitchen takes the higher value, 2%. BS 8206-2 has been withdrawn and replaced in the UK by BS EN 17037, but these figures are still widely cited in planning reports, which is why the calculator checks them and says so next to the result.
The results also check the Australian NCC 2022: Volume Two H4P4 asks for an average daylight factor of at least 2% in a habitable room. The EN 17037 lines are marked possible rather than meets, for the reason below. Targets are shown for information: check the edition in force and what your local authority asks for.
The European standard BS EN 17037 sets its minimum level as 300 lux over half of the reference plane and 100 lux over 95% of it, for at least half of the daylight hours. The daylight factor route turns the 300 lux into a target daylight factor using the median external diffuse illuminance of the site: DT = 300 / Ev,d,med × 100. The calculator includes four reference cities (Berlin 13,900 lux, Prague 14,900 lux, Bratislava 16,300 lux and Stockholm 12,100 lux) or your own value. For Prague, the default, the target is about 2.0%.
That check is indicative. EN 17037 asks for a value exceeded over half of the plane, while the average daylight factor is a mean, and a mean can be pulled up by a very bright zone next to the window. If the average falls below DT, the room is unlikely to meet the standard. If it is above, compliance is possible but not proven.
For homes in the UK, the National Annex to BS EN 17037 uses lower targets: 100 lux for bedrooms, 150 lux for living rooms and 200 lux for kitchens, over half of the plane. No UK illuminance value is built in, so choose Custom and enter the figure for your site.
The window to floor ratio (WFR) is glass area divided by floor area. The calculator shows it two ways: with the net glass, and with the gross opening including the frame. The window to wall ratio (WWR) is the gross opening area divided by the internal area of that wall, reported for each of the four walls, with the compass direction of each wall taken from the way the front wall faces.
Some codes use a ratio directly. The NCC 2022 Housing Provisions (10.5.1) ask for light transmitting glass of at least 10% of the floor area for windows, or 3% for roof lights, with a mix of the two combined in proportion. The calculator reports this as a score where 100% or more passes.
A ratio alone is not a daylight check. Two rooms with the same ratio can have very different daylight factors once you add an obstruction, low-E glass, a thick reveal or a deep plan, which is why the tool reports both. If you are working through window sizes for a whole project, our door and window schedule guide covers how to record them.
Room depth rule. For a room lit by windows in one wall only, the depth L should satisfy L/W + L/H ≤ 2/(1 − Rb), where W is the room width along the window wall, H is the height of the window head above the floor and Rb is the average reflectance of the surfaces in the rear half of the room. If it fails, the back of the room will look darker than the front, whatever the average says. The calculator shows Rb and the maximum depth the rule allows. With windows on more than one wall, or with a roof light, the rule does not apply and the result says n/a.
No-sky line. The no-sky line divides the part of the working plane that can see the sky through the window from the part that cannot. The calculator uses the section construction from the Code for Sustainable Homes guidance: d = x × h / y, where x is the distance to the obstruction, h is the height of the window head above the working plane and y is the height of the obstruction above the window head. It reports the share of the working plane with direct sky against a target of 80%, and the section drawing shows the line.
The obstruction is treated as continuous and parallel to the window. Roof lights are not included in the no-sky line, so in a room with roof lights the true share with direct sky is higher than reported.
The average daylight factor formula assumes a CIE overcast sky, a simple rectangular room and continuous obstructions. It ignores the sun, orientation and climate, so north and south facing rooms with the same windows score the same. The position of a window along its wall does not change the result.
Use it for early design, not as a substitute for simulation. For climate based metrics such as the EN 17037 illuminance method, spatial daylight autonomy or useful daylight illuminance, use validated Radiance based tools; our guide to daylight analysis software compares them. For direct sunlight and orientation, which the daylight factor leaves out, draw a chart with the sun path diagram generator.
With DF = T × Aw × θ × M / (A × (1 − R²)), where T is the glass transmittance, Aw the net glazed area, θ the visible sky angle, M the dirt factor, A the total room surface area and R the mean reflectance. The calculator does it for every window and adds the results.
BS 8206-2 suggested at least 1.5%, with 2% for kitchens and 1% for bedrooms. The standard has been withdrawn, but many planning reports still quote these figures. In Australia the NCC asks for 2% in any habitable room.
No. EN 17037 uses illuminance targets linked to the local climate, so the target daylight factor depends on the site: about 2% for 300 lux in Prague, for example. The average daylight factor is a mean, so the comparison is indicative only.
The Australian NCC minimum is 10% for windows and 3% for roof lights. A ratio ignores obstructions, glass and depth, so check the daylight factor too.
The line on the working plane beyond which no sky can be seen through the window. Areas behind it look gloomy, which is why a common target is direct sky on at least 80% of the working plane.
Use it for early design and to check sketches. Planning reports in the UK normally need a BRE 209 assessment by a specialist, often with simulation.
Yes, with no sign up. It runs in your browser and nothing is sent to a server.